Pharma Cleanroom
Run a GMP sterile suite with Grade B, C, D and gowning cleanrooms, a pressure cascade, make-up air, a chilled-water plant, and door and filter faults.
A GMP sterile manufacturing suite. Four cleanrooms (Grade B, Grade C, Grade D and the gowning room) hold a pressure cascade against the corridor. Two make-up air units, a duty/standby chilled-water plant and a clean steam stand-in support them. Every cleanroom's makeup_air_temp input is bound to makeup-air-001 supply_air_temp, so a make-up unit fault leaks a few tenths of a kelvin into the rooms.
Each room has its own air change rate and pressure setpoint. Door events, shift activity and filter loading move pressure and particle counts the way a quality team watches them. The 24-hour profile runs two production shifts with breaks, then overnight cleaning.
Ages are mixed: the gowning room at 8,500 hours, Grade C at 6,000, Grade B at 3,000 and Grade D at 1,000. Both chillers are young (40 and 5 hours) because the chiller lifecycle is measured in tens of hours.
What's running
| Area | Assets |
|---|---|
| Cleanrooms | Grade B, Grade C, Grade D and gowning zones |
| Make-up air | 2 rooftop units |
| Utilities | 2 chillers, 2 chilled-water pumps, buffer tank, clean steam stand-in |
| Model | Count | Assets |
|---|---|---|
cleanroom-zone | 4 | see below |
hvac-rtu | 2 | makeup-air-001, makeup-air-002 (23.5 °C setpoint, the lowest the model allows) |
industrial-chiller | 2 | chiller-001 (duty), chiller-002 (standby), 200 kW, 6.5 °C supply |
centrifugal-pump | 2 | chw-pump-001, chw-pump-002 |
storage-tank | 1 | chw-buffer-001 (5,000 L) |
hot-water-boiler | 1 | clean-steam-001 (300 kW) |
| Zone | Air changes | Pressure vs corridor | Volume |
|---|---|---|---|
zone-b-001 (Grade B) | 50 ACH | 40 Pa | 120 m³ |
zone-c-001 (Grade C) | 25 ACH | 30 Pa | 300 m³ |
zone-d-001 (Grade D) | 15 ACH | 20 Pa | 450 m³ |
gowning-001 (gowning) | 12 ACH | 10 Pa | 80 m³ |
The pressure alarm trips 10 Pa below each setpoint (30, 20 and 10 Pa) and at 5 Pa in the gowning room. Gowning is monitored with Grade D limits.
Clean steam is an approximation
Miravo has no clean steam generator model. clean-steam-001 is a hot-water
boiler at a 100 °C setpoint and 3 bar. It produces hot water, not steam.
Hierarchy
pharmaco / sterile-plant
├── cleanrooms
│ ├── grade-b: zone-b-001
│ ├── grade-c: zone-c-001
│ ├── grade-d: zone-d-001
│ └── gowning: gowning-001
├── make-up-air
│ └── rooftop-units: makeup-air-001, makeup-air-002
└── utilities
├── chilled-water: chiller-001, chiller-002, chw-pump-001, chw-pump-002, chw-buffer-001
└── clean-steam: clean-steam-001What to watch
differential_pressureon each zone. The 10 Pa steps between adjacent grades are the cascade. It dips on door events and falls when airflow drops.air_changes_per_houragainst the target, andhepa_filter_dp, which rises with wear and loading.room_temperatureandrelative_humidityagainst the setpoints.particle_count_0_5um,particle_count_5umanddoor_open. Each room carries its own Annex 1 action limits, so Grade B alarms at 352,000 / 2,930 per m³ in operation and 3,520 / 29 at rest, while Grade D and gowning use 3,520,000 / 29,300.excursion_countper room, withdp_excursion_count,temp_excursion_count,rh_excursion_countandparticle_excursion_count. A simulated week with the shipped random faults gives each room a handful to about ten excursions, mostly pressure alarms from door and fan events. Ask "how many excursions, and on which rooms" by comparing the counters across the four zones.- Chiller
supply_tempandcompressor_stage.chiller-001is the duty unit: supply regulates to the 6.5 °C setpoint with about 3 K delta-T at the default 50% load, and the stages cycle with the daily load swing.chiller-002is the standby (standby_unit: 1, itsduty_compressor_stageinput bound tochiller-001compressor_stage): it idles at stage 0 until the duty chiller stops or trips (miravo inject chiller-001 compressor_failure), then takes the full load within seconds.
Faults to try
Commands assume miravo start -t pharma-cleanroom.
miravo inject zone-b-001 pressure_cascade_lossThe key GMP alarm. The pressure target drops 20 Pa, so Grade B goes from about 40 Pa to about 20 Pa for 15 simulated minutes.
miravo inject zone-b-001 hepa_filter_loadingFilter loading. hepa_filter_dp climbs from about 250 Pa towards 370 Pa and supply_airflow falls. The weaker airflow also pulls differential_pressure down.
miravo inject zone-d-001 humidifier_failurehumidifier_output drops to zero and relative_humidity drifts from about 50 % to under 30 %.
miravo inject zone-c-001 door_left_openThe door stays open for 4 simulated minutes while staff are active. The cascade collapses and particle_count_0_5um climbs. It waits for shift activity above 0.3, so it can start a moment after you inject it.
miravo inject zone-b-001 supply_fan_degradedThe fan delivers about 70 % of its reference for 30 simulated minutes. Grade B pressure goes negative, dp_alarm asserts after about 2 minutes, and 5 µm counts pass the in-operation action limit: excursion_count goes up by one while dp_excursion_count and particle_excursion_count both count.
Clear any of them with --clear, for example miravo inject zone-b-001 pressure_cascade_loss --clear.
Launch
Console ⭢ Catalog ⭢ Pharma Cleanroom ⭢ Launch. No restart required.
Verified
In Catalog, Pharma Cleanroom shows 12 assets and 6 models. The Assets page keeps updating after launch.
Next
Cleanroom zone model
Members, faults, and parameters of the cleanroom zone.
Connect a protocol
Hook a downstream system to the running factory.
Map into Litmus Edge
Map this template into Litmus Edge.
Was this page useful?
Last updated on
District Heating
Run a city heat network with gas boilers, a thermal accumulator, trunk pumps and four customer substations, each with seasonal demand and its own pipe delay.
Models
Browse the 13 built-in asset models: pumps, motors, tanks, compressors, boilers, generators and other reusable equipment.
Miravo